Replacing Weidmüller and restoring TPEM ↔ Siemens communication
100% remote replacement of an unavailable Weidmüller communication controller with an OWEN PLC210, restoring Modbus RTU/TCP communication between TPEM and Siemens S7-1500.
Task
Since March, communication between two gas-piston generator units, each with its own TPEM control system, and the higher-level Siemens S7-1500 had been disrupted due to a failed Weidmüller communication controller. A direct replacement was not possible because the required hardware and software were unavailable. The task was to develop a modern replacement, restore data exchange and return the installation to operation without rebuilding the existing control system.
Technical data
- OWEN PLC210
- CODESYS V3.5
- Siemens S7-1500
- TPEM
- Modbus RTU
- Modbus TCP
- 2 analog signals
- 543 Siemens register positions
- 141 TPEM parameters
- 71 event and alarm messages
- 100% remote implementation
Work performed
- Analysis of the existing TPEM / Weidmüller / Siemens S7-1500 architecture and source documentation
- Work with German original software and technical documentation; communication in German, Russian and English
- Development of a replacement solution based on OWEN PLC210 and programming in CODESYS V3.5
- Modbus RTU communication with TPEM and Modbus TCP communication with the Siemens S7-1500
- Integration of an additional analog input module and two analog signals
- Preparation of electrical diagrams, connection drawings and dismantling / retrofit instructions
- Preservation of the existing Siemens data structure and implementation of the required data conversion
- Remote support for the customer’s technicians during installation and rewiring
- Verification of 543 Siemens register positions, 141 TPEM parameters and 71 event / alarm messages
Result
- The installation was restored without a complete rebuild of the existing control system
- The unavailable Weidmüller controller was replaced with a modern programmable solution
- TPEM ↔ Siemens S7-1500 communication was restored via Modbus RTU / TCP
- The existing Siemens data structure was preserved
- The entire project was completed 100% remotely with no on-site visit required
- After receiving the complete source documentation, the solution was developed and commissioned in approximately one week